The product is priced upon contact.
Specifications
Two-stage progressive or analog operation. (Analog operation is achieved by adding a PID controller and a temperature or pressure sensor that are offered separately.)
Low emissions Low NOx and CO (Class 2).
Ability to achieve optimal combustion values by adjusting air and head position.
Easy maintenance due to the fact that the dispersion unit is accessible without the need to remove the burner from the boiler.
High back pressure with low electrical consumption and low noise level.
Long pipe with rolling flange to adapt the burner to any type of boiler.
Air intake adjustment damper with electric servo motor.
Damper with total block at the burner pauses to reduce thermal losses.
Air intake made of sound-absorbing material, designed for optimal linearity during opening.
CE gas line equipped with: Operating and safety solenoid valve, minimum gas pressure switch, pressure regulator and gas filter.
Possibility of integrating a Leakage Control valve.
Mistake-proof quick connectors for burner and gas line connection.
Gas line connection from below.
Ionization electrode for flame detection and provision for micro-ammeter (mA) connection.
Seven-pole quick connector for electrical and thermostatic connection.
Four-pole quick coupler to control 2nd stage or PID controller.
Degree of electrical protection IP44.
Electric panel made of cast aluminum with electrical protection degree IP55.
General characteristics
Minimum thermal power kW 400
Maximum thermal output kW 2100
Minimum delivery kg/h 40
Maximum flow rate kg/h 210
Motor power kW 3.0
Power supply N 3
Frequency Hz 50
Electrical voltage V 400
Package dimensions mm 1070x800x700
Weight kg 94