Reference: 02617
5000 LITERS UNDERGROUND LIQUID GAS TANK
Send to all Greece
Returns Policy
Use of SSL Encryption
Italian Remanufactured LPG Tank
Legislation: manufactured according to Directive 2014/68/EU
Construction Code: AD 2000 MERKBLATT
Sheet Metal Type: P355 NH(6.5mm)
Operating Pressure: 17.65 bar
Operating Temperature: -20°C - +50°C
Underground Tank Paint:
1. One Coat of Two-Component Zinc
2. Two Coats of SMALTOTANK GP
The technical file of each tank contains the DECLARATION OF CONFORMITY, the hydraulic test, the insurance certificate and the instructions for use.
It has CE marking as well as ISO 9001:2015 and the quality and suitability control is carried out by a certification body if a hydraulic test and ultrasound have been performed beforehand.
It should be noted that every 5 years a visual inspection and thickness measurement is required and every 10 years a safety valve change by a specially authorized body.
TANKS WARRANTY
The tank Warranty depends on its correct installation (in accordance with the requirements of the European Community), its good use (instructions for use are provided with the technical file), the environmental conditions and the acidity of the soil.
Therefore, taking into account all of the above, as well as the technical study and the suppliers' warranty for the tank accessories, we conclude the following:
SHELL 15 TO 25 YEARS
PAINT 5 TO 15 YEARS
SAFETY VALVE 10 YEARS
MULTIVALVE, LIQUID PHASE VALVE, FILLING VALVE 5 YEARS
MAGNETIC LEVEL INDICATOR 5 YEARS